A gas network operator needed a full PD CLC/TR 50427 assessment after its own screening flagged a broadcast transmitter near one of its sites.
The challenge. A gas network operator’s own screening flagged a broadcast transmitter close to one of its gas installations. Radio energy picked up by metal structures can cause a spark, and with a flammable atmosphere possible on site, the operator needed a full assessment to PD CLC/TR 50427, the guide HSE treats as relevant good practice.
What we did. Rather than rely on the earlier screening, we carried out an independent search for every fixed transmitter within the 17.9 km vulnerable zone for natural gas, which found 77. Of those, 76 were eliminated at the initial assessment stage. For the remaining one, the broadcast transmitter, we carried out the full calculation of section 10.4 and confirmed field levels with a site survey.

The outcome. The calculated extractable power was 7.9 mW against the 6 W ignition threshold for natural gas, a safety margin of over 700 times, confirmed by an independent upper-bound check. The site was assessed as no risk, with a documented, standard-based result the operator could place straight into its DSEAR records.