A plastics manufacturer needed to know whether its new 305 kW drive motors, and the rest of the site, were safe for staff under CEMFAW, including workers with implants.
The challenge. A UK manufacturer had installed large new production line drive motors: 305 kW, inverter-fed, drawing nearly 600 A. Its health and safety team needed to know whether staff working near them were safe under the Control of Electromagnetic Fields at Work Regulations 2016 (CEMFAW), and how the rest of the site measured up.
What we did. We surveyed the whole site, not just the motors. That covered magnetic separators and plate magnets on the production lines, MIG welding and an induction bearing heater in the workshops, forklift charging areas, and the main electrical supplies. Each source was measured and compared with the CEMFAW action levels and the public reference levels used for workers at particular risk, including those with pacemakers and other implants.

The outcome. The survey gave the site a clear picture of every significant source. At the drive motors, fields exceeded the public reference levels only within 20 cm of the casing. We set a simple 0.2 m exclusion zone for workers at particular risk, so the site could protect implant wearers without restricting anyone else’s work.