Case study: EMC assessment of an 11 kV cable crossing over a railway bridge

A utility contractor needed Network Rail to accept two new 11 kV circuits crossing a bridge above an operational London station.

The challenge. The circuits were to run across a road bridge spanning platforms, track, and signalling and telecoms cables. Network Rail needs evidence that new HV cables will not interfere with train detection, signalling or communications, and a short statement that the risk is low is not enough. The contractor needed a calculation-based assessment that would be accepted first time.

What we did. We carried out a desk-based EMF and EMC assessment, with no site visit needed. We modelled the 50 Hz magnetic fields from both circuits at their full rated current of 418 A, far above the expected load. We compared the results with the CEMFAW Action Level of 1000 µT and the public Reference Level of 100 µT. We then assessed the risk to track circuits, signalling and telecoms cables against the EN 50121 railway EMC standards. Comparative modelling showed that laying the cables in trefoil cut the external field by more than ten times compared with single cores laid flat.

Colour map of the calculated 50 Hz magnetic field around two 11 kV trefoil cable circuits, showing the field falling quickly with distance from the cables.
Calculated 50 Hz magnetic field around two 11 kV trefoil circuits at 400 A. The field falls quickly with distance.

The outcome. Even at full rated current, the field 60 cm from the cables was below the 100 µT public Reference Level. At the railway assets, 4 m or more below, it fell to under 1 µT, and induced voltages in railway cables were in the microvolt range. No mitigation was needed, Network Rail accepted the report without comment, and the installation went ahead.

Case study: A magnetic sculpture on its way to an international art fair

A gallery needed to know whether a magnetic sculpture was safe to show and handle before sending it to an international art fair.

The challenge. A London gallery was preparing to show a sculpture built around large permanent drum magnets at a major international art fair. Before shipping, it needed to know whether the work posed any risk to visitors, to staff handling it, or to people with pacemakers and other implants, and whether warning signs or barriers would be required.

What we did. We visited the gallery and mapped the static magnetic field around the work and its packing crate. We measured how quickly the field fell away with distance and checked for attraction on everyday steel objects.

Simple handling guidance travels with the work to every venue.

The outcome. The field fell below 0.5 mT within 9 cm of the work, and the crate exterior was below 0.5 mT everywhere. Visitors faced no risk, and no warning signage was needed. The one sensible precaution was to ask handlers whether they had an implant, keeping them 9 cm away or passing the job to a colleague. Alongside the report we provided a plain-English slide summary and a one-page handling note designed to travel with the work to each new venue.

Case study: Siting a radiotherapy linac at a hospital

A hospital needed to confirm that a nearby railway and MRI suite would not stop a new radiotherapy linac meeting its manufacturer’s static magnetic field limit.

The challenge. A hospital planned a new bunker for a radiotherapy linear accelerator (linac). The manufacturer requires the machine to sit outside any static magnetic field above 100 µT. The site lies close to a railway line and an existing MRI suite, both potential sources of strong static fields. The architects needed to know whether the chosen location would work before construction started.

What we did. We logged the static magnetic field at twelve positions with a three-axis magnetometer, including the bunker corners, the ground nearest the railway and a transect towards the MRI room. We established the local background and assessed the effect of passing trains on the Earth’s field.

Radiotherapy linear accelerator treatment room
A linac must be sited away from strong static magnetic fields.

The outcome. Fields across the bunker footprint were 38–53 µT, well under the 100 µT criterion, giving a margin of at least 47 µT at the isocentre. The only reading above 100 µT was at the MRI room wall, outside the footprint. The location was confirmed as suitable, with follow-up checks recommended once the structural steel is in place and before commissioning.

Case study: Magnetic shielding for an electron microscope production floor

Buried power cables were disturbing electron microscopes on a production floor. We measured how far shielding could realistically bring the fields down.

The challenge. A high-technology manufacturer was seeing interference on electron microscopes on its production floor. The suspected cause was 50 Hz magnetic fields from buried 400 V circuits beneath the floor, at around 1 µT at floor level. The company wanted to know whether those fields could be brought down towards 0.1 µT.

What we did. We measured the fields over the buried conductors and reported on the options for reducing them. We then assessed the shielding options and measured their real-world performance on site, testing mu-metal and several thicknesses of a commercial shielding fabric over the problem conductors.

Shielding materials were tested on site over the problem conductors.

The outcome. The measurements showed that a tenfold reduction was not practical at floor level. A threefold reduction was achievable, and we set out what that would involve in cost and disruption, so the client could weigh it against other options. Each stage was reported with a short slide summary for the decision-makers.

Case study: High-voltage cables across a public bridge to a data centre

Before a data centre’s power supply was built, the design team needed proof that magnetic fields from high-voltage cables on a public bridge would stay within the public limits.

The challenge. A new data centre was to be supplied by high-voltage cables routed across a bridge open to the public. The engineering consultancy designing the route needed to show that magnetic fields on and around the bridge would be within the public exposure limits, before the design was finalised.

What we did. We modelled the magnetic fields from the cables in trefoil inside steel ducts, using the worst-case loading of one circuit at 568 A. We calculated fields at every accessible position on and near the bridge and compared them with the 100 µT public reference level. A follow-up study assessed whether shielding would be needed.

Calculated fields let a design be checked before anything is built.

The outcome. The assessment showed the 100 µT reference level would not be exceeded anywhere the public could reach, so no additional shielding was required. The design team had calculated, documented evidence of compliance, without a site survey and before anything was built. When later design changes were proposed, the same model could be re-run to check them.

Case study: Whole-site EMF survey at a plastics manufacturing plant

A plastics manufacturer needed to know whether its new 305 kW drive motors, and the rest of the site, were safe for staff under CEMFAW, including workers with implants.

The challenge. A UK manufacturer had installed large new production line drive motors: 305 kW, inverter-fed, drawing nearly 600 A. Its health and safety team needed to know whether staff working near them were safe under the Control of Electromagnetic Fields at Work Regulations 2016 (CEMFAW), and how the rest of the site measured up.

What we did. We surveyed the whole site, not just the motors. That covered magnetic separators and plate magnets on the production lines, MIG welding and an induction bearing heater in the workshops, forklift charging areas, and the main electrical supplies. Each source was measured and compared with the CEMFAW action levels and the public reference levels used for workers at particular risk, including those with pacemakers and other implants.

Large industrial electric motor in a plant room
Large inverter-fed drive motors can produce strong magnetic fields close to the casing.

The outcome. The survey gave the site a clear picture of every significant source. At the drive motors, fields exceeded the public reference levels only within 20 cm of the casing. We set a simple 0.2 m exclusion zone for workers at particular risk, so the site could protect implant wearers without restricting anyone else’s work.

Case study: RF ignition assessment at a natural gas installation

A gas network operator needed a full PD CLC/TR 50427 assessment after its own screening flagged a broadcast transmitter near one of its sites.

The challenge. A gas network operator’s own screening flagged a broadcast transmitter close to one of its gas installations. Radio energy picked up by metal structures can cause a spark, and with a flammable atmosphere possible on site, the operator needed a full assessment to PD CLC/TR 50427, the guide HSE treats as relevant good practice.

What we did. Rather than rely on the earlier screening, we carried out an independent search for every fixed transmitter within the 17.9 km vulnerable zone for natural gas, which found 77. Of those, 76 were eliminated at the initial assessment stage. For the remaining one, the broadcast transmitter, we carried out the full calculation of section 10.4 and confirmed field levels with a site survey.

Metal structures on site can pick up radio energy from nearby transmitters.

The outcome. The calculated extractable power was 7.9 mW against the 6 W ignition threshold for natural gas, a safety margin of over 700 times, confirmed by an independent upper-bound check. The site was assessed as no risk, with a documented, standard-based result the operator could place straight into its DSEAR records.