Expectant mothers at work: have the EMF answer ready

An expectant mother is one of the workers the law singles out for special consideration. The EMF thresholds that protect her are several times lower than those for the general workforce, and the most sensitive weeks are often before anyone at work has been told. This short video and the guide below explain what the law requires, where to look, and how to have the answer ready.

What the law requires

Two sets of duties apply. The Management of Health and Safety at Work Regulations 1999 (regulation 16) require the risk assessment to cover risks to new and expectant mothers, and non-ionising radiation is one of the physical agents to consider. The Control of Electromagnetic Fields at Work Regulations 2016 and the HSE’s guidance single out expectant mothers as workers at particular risk.

“You must give special consideration to the safety of employees at particular risk (even if you are in compliance with the exposure limits).”
HSE HSG281, paragraph 49

Why the map must come first

The most sensitive weeks of a pregnancy are often before anyone at work has been told. So the time to find out where the higher fields are is before you need the answer.

  • Before. Map the areas above public reference levels, and tell staff the map exists.
  • Notified. Check her tasks and routes against the map, and agree any changes.
  • During. Keep the changes in place, and review them if her work changes.
  • Return. Restore normal duties and record the review.

Much lower thresholds

The unborn child is not an employee, so her exposure is usually kept within the public reference levels in Council Recommendation 1999/519/EC. These are between 5 and 50 times lower than the values for the general workforce.

FieldPublic levelWorkforce valueHow much lower
Static magnetic field40 mT2,000 mT (ELV)50×
50 Hz magnetic field100 µT1,000 µT (Low Action Level)10×
RF heating (whole body)0.08 W/kg0.4 W/kg (SAR ELV)5×
RF power density, 10–400 MHz2 W/m²10 W/m² (Action Level)5×

Where to look

Most areas of most sites are well below the public levels, and office equipment, phones and Wi-Fi are not a concern. The zones that matter are close to particular industrial sources:

  • Induction heaters and furnaces
  • Radio transmitters and antennas
  • RF plastic welders and sealers
  • MRI and NMR magnets
  • Switchboards and transformers
  • Resistance and arc welding
  • Large motors and drives
  • Microwave heating and drying

With a site map in place, each notification is a desk review, not a new survey.

A simple decision path

  • Does her work take her into areas above public reference levels? If not, no change is needed. Record it and tell her.
  • If it does, can the task or route change so she stays below them? If so, adjust her duties or access for the pregnancy.
  • If not, offer suitable alternative work. Suspension on full pay is the legal backstop.

Suitable alternative work, and suspension on full pay where none is available, are rights under the Employment Rights Act 1996.

Common misunderstandings

  • “We’ll deal with it when someone tells us.” The most sensitive weeks are often before anyone has been told. Map the site first.
  • “She should avoid all electrical equipment.” Most of most sites is well below the public levels. Only a handful of zones near particular sources matter.
  • “Phones and Wi-Fi are a worry.” Office equipment, phones and Wi-Fi are well below the public reference levels.
  • “Every notification needs a new survey.” With a site map in place, it is a desk review.

In short

Map once. Then every notification gets a quick, confident answer, and nobody is moved off work they could safely do.

The same lower thresholds matter for workers with implanted devices: see Pacemakers at work: the people the EMF limits don’t cover. For how all these numbers fit together, see Action Levels, ELVs and reference levels.

Pacemakers at work: the people the EMF limits don’t cover

The EMF exposure limits at work are set for the general workforce. They do not protect people with pacemakers, defibrillators or other implanted and body-worn medical devices. Those workers need much lower thresholds, and the places where those thresholds are exceeded are usually close to ordinary equipment, not exotic sources. This short video and the guide below explain who is at risk, how much lower the thresholds are, and what to do about it.

Who is at particular risk

The HSE’s guide to the Control of Electromagnetic Fields at Work Regulations 2016, HSG281, names these workers specifically.

“You must make sure you take employees at particular risk, such as expectant mothers and workers with active or passive implanted or body-worn medical devices, into account …”
HSE HSG281, paragraph 12 (extract)

There are three groups, each with a different risk:

  • Active implants. Pacemakers, defibrillators, neurostimulators and cochlear implants. Interference can make the device pause, deliver a shock or reset.
  • Body-worn devices. Insulin pumps, glucose monitors and other worn electronics. Interference can affect readings or drug delivery.
  • Passive implants. Joint replacements, plates, pins and stents. These can heat up in strong RF and induction fields, and feel forces near strong magnets.

Much lower thresholds

Implanted devices are designed to work normally in fields up to the reference levels for the general public in Council Recommendation 1999/519/EC. EN 50527-1, the standard for assessing workers with implants, uses those levels as its starting point. For static fields, a specific threshold of 0.5 mT applies. Interference is instantaneous, so readings are compared without time averaging.

FieldImplant thresholdWorkforce valueHow much lower
Static magnetic field0.5 mT2,000 mT (ELV)4,000×
50 Hz magnetic field100 µT1,000 µT (Low Action Level)10×
50 Hz electric field5 kV/m10 kV/m (Low Action Level)2×
Radiofrequency, 100 MHz28 V/m61 V/m (Action Level)2×

Distance is the main control

Fields around most workplace equipment fall away quickly with distance. Near a typical source, the 50 Hz magnetic field can drop below the 100 µT implant threshold within about a metre. So the usual answer is a clearly marked zone rather than new equipment or shielding.

A signed boundary also protects the people you don’t know about: visitors, contractors, and staff who have not told you about a device.

A practical approach

Five steps cover most sites:

  • Identify. Invite confidential disclosure through occupational health.
  • Map. Survey where fields exceed implant thresholds.
  • Mark. Put in zones, signs and inductions for staff, visitors and contractors.
  • Check. Carry out an individual assessment with device data where needed.
  • Review. Look again when there is a new device, new equipment or a change of layout.

Common misunderstandings

  • “Modern pacemakers are shielded.” They are designed to cope with fields up to public reference levels, not with workplace fields that can be many times higher.
  • “We’d know if anyone had one.” Workers do not have to tell you. Invite confidential disclosure, and sign zones so everyone is covered.
  • “A quick walk past is fine.” Interference is instantaneous. Brief exposure above the threshold can still affect a device.
  • “Leave it to their cardiologist.” Cardiologists know the device, not your site. They need your field data to advise.

In our experience

Almost every site has areas above implant thresholds, usually close to everyday equipment: switchboards, cables, motors, welders and induction heaters. Most can be managed with a marked zone and a short briefing.

For how implant thresholds compare with the other numbers in an EMF report, see Action Levels, ELVs and reference levels: what the numbers mean.

EMF assessments at work: what UK employers need to know

The Control of Electromagnetic Fields at Work Regulations 2016 (CEMFAW) require UK employers to assess the electromagnetic fields (EMF) their employees are exposed to. Many employers don’t know the Regulations exist, and others aren’t sure whether they apply to them. These are the questions we’re asked most often by employers looking for an EMF assessment.

Do I need an EMF assessment?


Yes, if your employees work with or near equipment that produces electromagnetic fields. That covers almost every employer. Under the Control of Electromagnetic Fields at Work Regulations 2016 (CEMFAW), every employer must assess the levels of EMF their employees may be exposed to.

For most offices and low-risk workplaces, the assessment can be short and simple. For sites with higher-field equipment, it needs measurements or calculations, and a written record. Examples include induction heating, welding, electrolysis, high-current busbars, transformers and substations, RF heating and sealing, radio transmitters, MRI and research magnets.

What does an EMF assessment involve?


An EMF assessment identifies every significant EMF source on site, finds out how strong the fields are where people work, and compares them with the legal limits. Those limits are the action levels (ALs) and exposure limit values (ELVs) set by the Regulations. At the 50 Hz power frequency, for example, the low action level for magnetic fields is 1000 µT and the high action level is 6000 µT. For electric fields, the low action level is 10 kV/m and the high action level is 20 kV/m.

A typical assessment starts with a review of the site, the equipment and how people work around it. The fields are then measured with calibrated instruments, or calculated and modelled where measurement isn’t practical, and the results are compared with the action levels and exposure limit values. The assessment identifies any areas where workers at particular risk need extra care, and finishes with practical recommendations, such as signage, exclusion zones or changes to working practice.

Can we do the EMF assessment ourselves, or do we need a consultant?


Many employers can do a basic EMF assessment themselves, using HSE guidance (HSG281) and manufacturers’ information. A specialist is needed when the site has high-field equipment, when the information available isn’t enough to show compliance with CEMFAW, or when an employee has an implanted medical device.

If you’re not sure which applies to you, that uncertainty is itself a sign that specialist advice is worth having. A wrong answer either way costs money: unnecessary restrictions on one side, unprotected workers on the other.

What about employees with pacemakers or other implants?


Employees with pacemakers, ICDs and other active implanted medical devices are classed as workers at particular risk under CEMFAW, and they need a specific EMF assessment.

The legal limits for the general workforce don’t protect them, because fields well below the action levels can still interfere with an implanted device. An implant assessment looks at the employee’s actual work areas and tasks, compares the fields there with the levels the device can tolerate, and identifies any areas they should avoid. This lets them return to work, or stay in work, safely.

We carry out dedicated pacemaker and implanted device assessments for employers across the UK.

How long does an EMF assessment take, and what do we get at the end?


Most sites need a single day on site. Large or complex sites may need longer.

At the end you receive a written report that you can show to the HSE, your insurer or your client. It sets out what was assessed, the methods and standards used, the results against the CEMFAW action levels and exposure limit values, and clear recommendations. We also provide a short slide summary of the findings for managers who need the headlines.

How do I choose a competent EMF assessor?


Look for proven expertise in EMF specifically, not just general health and safety. EMF assessment is unregulated: anyone can buy a meter and call themselves an assessor.

Before you appoint anyone, ask about their qualifications in electromagnetics or radiation protection, and whether they belong to a recognised professional body such as the Society for Radiological Protection. Ask which measurement and calculation standards they will use, whether they can assess workers with implanted medical devices, and whether they can calculate or model fields as well as measure them. Ask to see an example report.

A good report doesn’t just list numbers. It compares them with the correct CEMFAW limits and tells you clearly what to do.

How often should an EMF assessment be reviewed?


CEMFAW requires you to review your EMF assessment whenever something significant changes. Examples include new equipment, a new layout, new working practices, or an employee with an implanted device joining or returning to work.

Even if nothing obvious has changed, it makes sense to review the assessment every few years so that it stays an accurate record of your site.

About EMFcomp

EMFcomp is an independent UK consultancy that specialises in EMF safety. We carry out EMF assessments for compliance with CEMFAW, EMF surveys, EMF modelling, implanted device assessments and RF ignition assessments for employers across the UK and internationally.

Our assessments are led by Dr Richard Findlay, who has a PhD in electromagnetics and around 30 years’ experience in EMF safety. He is a Certified Radiation Protection Professional, a Fellow and Past Chair of the EMF Safety Committee of the Society for Radiological Protection, and a member of ICES and the IRPA Non-Ionising Radiation Task Group.

To discuss an EMF assessment, email enquiries@emfcomp.com with a short description of your site and equipment.

Action Levels, ELVs and reference levels: what the numbers in an EMF report mean

EMF reports quote Action Levels, exposure limit values and reference levels, often on the same page. They are not interchangeable. Confusing them can lead a report to declare a site compliant while missing the people most at risk, or to raise alarm over a reading that is not a breach at all. This short video and the guide below explain what each number means, who it protects, and how a good report should set them out.

Outside the body, and inside it

The legal limits in the Control of Electromagnetic Fields at Work Regulations 2016 are the exposure limit values (ELVs). They apply to what happens inside the body: the electric field induced in tissue at low frequencies, and heating, measured as the specific absorption rate (SAR), at radio frequencies. These cannot be measured in a person, so they are calculated with computer models of the human body.

So the Regulations also set Action Levels. These are field strengths in the workplace that can be measured with an instrument. They are set so that if they are met, the ELVs are met too.

  • Action Levels (outside the body). Electric field (V/m), magnetic flux density (µT) and, at radio frequencies, power density (W/m²). Measured with an instrument.
  • Exposure limit values (inside the body). Induced electric field (V/m) and specific absorption rate (W/kg). Calculated with body models.

What a reading tells you:

  • Below the Action Level. The ELV is met. No further work is needed for the general workforce.
  • Above the Action Level. Not yet a breach. Calculate the ELV before drawing any conclusion.

Who each number protects

The Action Levels are set for the general workforce. They do not protect people with pacemakers or other active implants, or expectant mothers, who must be given special consideration under the HSE’s guide to the Regulations, HSG281.

“You must give special consideration to the safety of employees at particular risk (even if you are in compliance with the exposure limits).”
HSE HSG281, paragraph 49

For these workers, the lower reference levels for the general public in Council Recommendation 1999/519/EC are used. At 50 Hz, the magnetic field threshold for workers at particular risk is ten times lower than the Low Action Level.

Threshold at 50 HzApplies toMagnetic fieldElectric field
Reference levelWorkers at particular risk100 µT5 kV/m
Low Action LevelSensory effects1,000 µT10 kV/m
High Action LevelHealth effects6,000 µT20 kV/m
Limb Action LevelArms and legs only18,000 µTn/a

These are the values at 50 Hz, the frequency of mains electricity. All of them change with frequency. At 100 MHz (FM radio), for example, the electric field Action Level is 61 V/m and the reference level 28 V/m.

What a result means in practice

A measured value only means something when it is compared with the right threshold. The same reading can be unremarkable for most staff and a real concern for one person. A good report shows the measured value, each threshold as a number, the percentage, and the outcome for each group of workers.

Location (illustrative 50 Hz results)Measured% of Low AL (1,000 µT)% of reference level (100 µT)Outcome
Office, first floor0.3 µT< 1%< 1%No restriction
Cable riser40 µT4%40%No restriction
Switchboard, front face220 µT22%220%Restrict access for workers at particular risk
Transformer enclosure, 0.2 m1,400 µT140%1,400%Calculate ELVs; keep-out zone

AL = Action Level. Where a Low Action Level is exceeded, the Regulations allow it in some circumstances, provided the ELVs are shown to be met or specified conditions are applied.

Four common confusions

“Above the Action Level means we’re breaking the law.” Not necessarily. The legal limits are the ELVs. Exceeding an Action Level means more assessment, usually by calculation.

“Below the Action Levels, so it’s safe for everyone.” It is safe for the general workforce. Workers with implants and expectant mothers need the lower reference levels.

“The report says it meets ICNIRP.” Which values? ICNIRP publishes occupational and public levels, in 1998 and 2010 versions. Ask for the numbers applied.

“One measurement covers the site.” Limits depend on frequency. A 50 Hz reading says nothing about a radio transmitter or an induction heater.

What we see in practice

The reports that cause problems tend to share the same faults: limits that are not stated, a bare claim of “ICNIRP compliance” with no numbers behind it, and sites declared compliant with no thought for anyone with a pacemaker. None of that is obvious to the reader until something goes wrong.

A sound report leaves no room for doubt. Every result sits next to the threshold it was compared with, the frequency is stated, and the outcome is given separately for the general workforce and for workers at particular risk.

In short: ask any EMF report three things: which limits it applied, stated as numbers; at what frequency; and for whom.

Sources: The Control of Electromagnetic Fields at Work Regulations 2016 (SI 2016/588). Directive 2013/35/EU, Annexes II and III. HSE (2016) Electromagnetic fields at work, HSG281. Council Recommendation 1999/519/EC. ICNIRP (1998, 2010) guidelines.

Choosing an EMF assessor: twelve questions to ask before you commit

Anyone can buy a meter and call themselves an EMF specialist. There is no accreditation scheme for EMF assessors, quotes vary widely, and a cheap assessment can look complete while missing the risks that matter. The legal duty stays with the employer either way. This short video and the guide below set out the questions worth asking any assessor before you commit.

The assessor

1. Who will actually do the work, and what is their track record in EMF? A credible assessor will say who they are, what they have done and for whom, and send an example report. If a quote says nothing about the person doing the work, ask why. Newcomers may be cheaper, but usually for a reason.

2. Is their expertise actually in electromagnetic fields? A general science or safety qualification is not enough, and experience in ionising radiation does not carry across: the physics, limits and methods are completely different. Ask how many workplace EMF assessments they have carried out.

3. What credentials do they hold, and who issued them? There is no accreditation scheme for EMF assessors, so be wary of web-based or unfamiliar “EMF certificates”. The meaningful recognised status is Chartered Radiation Protection Professional (CRadP), awarded by the Society for Radiological Protection.

4. Is EMF their core business, or a sideline? Some large general health and safety firms added EMF because they saw the enquiries coming in, not because they have the expertise. Ask who in the company has done this work before, and how often.

5. Do they offer home surveys or sell protection products? Firms that sell shielding or market “EMF surveys” to worried householders have an interest in finding problems. Fields in homes are generally weak and well within safety thresholds. An independent assessor sells neither products nor fear.

The equipment and method

6. What instruments will they use, and are they calibrated? Ask for the make and model of each instrument and its calibration certificate. Consumer “EMF meters” bought online are not designed for compliance work and cannot support a legal assessment.

7. Can they measure every kind of field on your site? Different kinds of field need different instruments. Fields from drives, welders and induction heaters are not simple sine waves and need the weighted-peak method described in the HSE’s guidance, HSG281.

FieldFrequencyTypical sourcesNeeds
Static0 HzMRI and NMR magnets, industrial magnets, DC busbars, electrolysisStatic magnetometer
Low frequency1 Hz – 100 kHzCables, transformers, motors and drives, welding, induction heatingLF analyser, weighted-peak method
Radiofrequency100 kHz – 300 GHzRadio transmitters and antennas, RF heaters and sealers, radar, satellite uplinksBroadband or selective RF meter

8. Will they assess workers at particular risk? People with pacemakers and other implants, and expectant mothers, are protected by much lower thresholds than the general workforce. An assessment that checks only the Action Levels can declare a site compliant while missing exactly the places that matter.

Example: 50 Hz magnetic field near a switchboard, measured at 500 µTThresholdResult
Checked against the Low Action Level only1,000 µT“Compliant”
Checked for workers at particular risk100 µTExceeded

At 50 Hz, the reference level in Council Recommendation 1999/519/EC is used to assess workers at particular risk. The same reading can pass one check and fail the other.

9. Will they cover your whole site, not just the obvious source? The duty covers employees wherever they work: electrical rooms, plant rooms, workshops and roofs, not just the machine that prompted the enquiry. Agree the full scope before the visit.

The report

10. Will the report give the numbers, the standards and a clear verdict? You should see the limits applied, stated as numbers, the measurement standards followed, and a plain answer: compliant or not, and against what. Ask to see a sample report.

11. Will it tell you what to do, and what you don’t need to do? A good report turns measurements into practical controls, such as separation distances, signage, procedures and review triggers, and says plainly where no action is needed.

12. Is the price fixed, and what does it include? Check whether the visit, report, any modelling, RAMS and follow-up questions are included. A short visit with a few spot readings is not a site-wide assessment.

Warning signs

  • No named assessor, no CV and no example report
  • A quote given without any questions about your site
  • “EMF certification” from an online course
  • Consumer meters, or no instrument details at all
  • No mention of pacemakers, implants or expectant mothers
  • Results without the limits they were compared against
  • Selling shielding, “protection” products or home surveys
  • Alarming language with no clear, practical actions

What we see in practice

Over the years we have seen reports with no limits stated, measurements made with instruments that could not see the fields actually present, and sites declared compliant with no thought for anyone with a pacemaker. None of that is obvious to a buyer until something goes wrong. These questions are worth asking of anyone, including us.

The short version: compare quotes on who will do the work, what they will measure with, whether they will consider the people most at risk, and what the report will tell you, not on price alone.

Sources: The Control of Electromagnetic Fields at Work Regulations 2016 (SI 2016/588). HSE (2016) Electromagnetic fields at work, HSG281. Council Recommendation 1999/519/EC.

Is an EMF assessment optional? What CEMFAW Regulation 5 requires

An EMF assessment is often treated as a “nice to know”, something to get round to if budget allows. It is not. Assessing electromagnetic field exposure is a legal duty on every employer under UK health and safety law. This short video and the guide below set out what the Regulations and the Health and Safety Executive actually say.

What the law says

“The employer must make a suitable and sufficient assessment of the levels of electromagnetic fields to which employees may be exposed.”
The Control of Electromagnetic Fields at Work Regulations 2016, regulation 5(1)

“The employer must review the assessment when— (a) there is reason to suspect it is no longer valid; or (b) there has been a significant change in the matters to which it relates …”
The Control of Electromagnetic Fields at Work Regulations 2016, regulation 5(4) (abridged)

The word is must, not “should” or “may”. Failing to comply with a duty in health and safety regulations is a criminal offence under section 33 of the Health and Safety at Work etc. Act 1974.

What the HSE expects in practice

The HSE’s guide to the Regulations, HSG281, turns the duty into five practical steps. Together they describe a continuing process, not a single survey.

  1. Assess. Measure or calculate the fields wherever employees work (regulation 5(1)).
  2. Compare. Check exposure against the exposure limits (HSG281, paragraph 32).
  3. Protect. Give special care to workers at particular risk (HSG281, paragraph 49).
  4. Act. Put an action plan in place where it is needed (HSG281, paragraph 12).
  5. Review. Revisit the assessment after any significant change or new information (regulation 5(4)).

“You must give special consideration to the safety of employees at particular risk (even if you are in compliance with the exposure limits).”
HSE HSG281, paragraph 49

In short: the question is not whether to assess EMF exposure, but whether the assessment you have is suitable and sufficient. If you have no assessment, you are not complying.

Four common misunderstandings

“It’s optional: nice to know, if there’s budget.” The employer “must make a suitable and sufficient assessment”. It is a duty, not a recommendation.

“We only need to look at the obvious equipment.” The duty covers “the levels of electromagnetic fields to which employees may be exposed”, wherever they work.

“Nobody here has a pacemaker.” Exposure must be assessed for all staff. People at particular risk, such as workers with medical implants and expectant mothers, come on top of that, and you may not know who they are.

“We had it checked years ago.” The assessment must be reviewed after “a significant change”: a move, new equipment, a new layout.

A recent example

A major energy company asked us to re-survey a test laboratory after it moved to a new site. Both its safety staff and its managers regarded EMF assessment as optional. The laboratory turned out to be safe for all staff, with one simple precaution kept for people with pacemakers. But the duty does not stop at the lab door: the rest of the site, where the same employees work, had never been assessed.

Our report set out the legal position, so that the safety team could take the remaining areas to management with the evidence behind them.

In our experience, almost every site has areas where the fields exceed the levels that protect workers with medical implants and expectant mothers, usually close to everyday equipment such as switchboards, cables, motors and welders, not just the obvious sources.

Need an assessment, or a second opinion on the one you have?

EMFcomp carries out independent EMF assessments to the Control of Electromagnetic Fields at Work Regulations 2016 for employers across the UK. Email enquiries@emfcomp.com with a short description of your site and we will tell you what a suitable and sufficient assessment would involve.

Sources: The Control of Electromagnetic Fields at Work Regulations 2016 (SI 2016/588), regulation 5, www.legislation.gov.uk/uksi/2016/588. HSE (2016) Electromagnetic fields at work: A guide to the Control of Electromagnetic Fields at Work Regulations 2016, HSG281, paragraphs 12, 32 and 49, www.hse.gov.uk/pubns/books/hsg281.htm. Health and Safety at Work etc. Act 1974, section 33. Extracts are reproduced verbatim and contain public sector information licensed under the Open Government Licence v3.0.

Case study: EMC assessment of an 11 kV cable crossing over a railway bridge

A utility contractor needed Network Rail to accept two new 11 kV circuits crossing a bridge above an operational London station.

The challenge. The circuits were to run across a road bridge spanning platforms, track, and signalling and telecoms cables. Network Rail needs evidence that new HV cables will not interfere with train detection, signalling or communications, and a short statement that the risk is low is not enough. The contractor needed a calculation-based assessment that would be accepted first time.

What we did. We carried out a desk-based EMF and EMC assessment, with no site visit needed. We modelled the 50 Hz magnetic fields from both circuits at their full rated current of 418 A, far above the expected load. We compared the results with the CEMFAW Action Level of 1000 µT and the public Reference Level of 100 µT. We then assessed the risk to track circuits, signalling and telecoms cables against the EN 50121 railway EMC standards. Comparative modelling showed that laying the cables in trefoil cut the external field by more than ten times compared with single cores laid flat.

Colour map of the calculated 50 Hz magnetic field around two 11 kV trefoil cable circuits, showing the field falling quickly with distance from the cables.
Calculated 50 Hz magnetic field around two 11 kV trefoil circuits at 400 A. The field falls quickly with distance.

The outcome. Even at full rated current, the field 60 cm from the cables was below the 100 µT public Reference Level. At the railway assets, 4 m or more below, it fell to under 1 µT, and induced voltages in railway cables were in the microvolt range. No mitigation was needed, Network Rail accepted the report without comment, and the installation went ahead.

Case study: A magnetic sculpture on its way to an international art fair

A gallery needed to know whether a magnetic sculpture was safe to show and handle before sending it to an international art fair.

The challenge. A London gallery was preparing to show a sculpture built around large permanent drum magnets at a major international art fair. Before shipping, it needed to know whether the work posed any risk to visitors, to staff handling it, or to people with pacemakers and other implants, and whether warning signs or barriers would be required.

What we did. We visited the gallery and mapped the static magnetic field around the work and its packing crate. We measured how quickly the field fell away with distance and checked for attraction on everyday steel objects.

Simple handling guidance travels with the work to every venue.

The outcome. The field fell below 0.5 mT within 9 cm of the work, and the crate exterior was below 0.5 mT everywhere. Visitors faced no risk, and no warning signage was needed. The one sensible precaution was to ask handlers whether they had an implant, keeping them 9 cm away or passing the job to a colleague. Alongside the report we provided a plain-English slide summary and a one-page handling note designed to travel with the work to each new venue.

Case study: Siting a radiotherapy linac at a hospital

A hospital needed to confirm that a nearby railway and MRI suite would not stop a new radiotherapy linac meeting its manufacturer’s static magnetic field limit.

The challenge. A hospital planned a new bunker for a radiotherapy linear accelerator (linac). The manufacturer requires the machine to sit outside any static magnetic field above 100 µT. The site lies close to a railway line and an existing MRI suite, both potential sources of strong static fields. The architects needed to know whether the chosen location would work before construction started.

What we did. We logged the static magnetic field at twelve positions with a three-axis magnetometer, including the bunker corners, the ground nearest the railway and a transect towards the MRI room. We established the local background and assessed the effect of passing trains on the Earth’s field.

Radiotherapy linear accelerator treatment room
A linac must be sited away from strong static magnetic fields.

The outcome. Fields across the bunker footprint were 38–53 µT, well under the 100 µT criterion, giving a margin of at least 47 µT at the isocentre. The only reading above 100 µT was at the MRI room wall, outside the footprint. The location was confirmed as suitable, with follow-up checks recommended once the structural steel is in place and before commissioning.

Case study: Magnetic shielding for an electron microscope production floor

Buried power cables were disturbing electron microscopes on a production floor. We measured how far shielding could realistically bring the fields down.

The challenge. A high-technology manufacturer was seeing interference on electron microscopes on its production floor. The suspected cause was 50 Hz magnetic fields from buried 400 V circuits beneath the floor, at around 1 µT at floor level. The company wanted to know whether those fields could be brought down towards 0.1 µT.

What we did. We measured the fields over the buried conductors and reported on the options for reducing them. We then assessed the shielding options and measured their real-world performance on site, testing mu-metal and several thicknesses of a commercial shielding fabric over the problem conductors.

Shielding materials were tested on site over the problem conductors.

The outcome. The measurements showed that a tenfold reduction was not practical at floor level. A threefold reduction was achievable, and we set out what that would involve in cost and disruption, so the client could weigh it against other options. Each stage was reported with a short slide summary for the decision-makers.